JKSSS+ Series - 42
JKSSS+ Series 2.3 - 4.2KV
5.1.9RTDConguration(SetpointPage9)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Use NEMA Temp for RTD Values Disabled Enabled or Disabled SP9.1
# of RTD Used for Stator 40-6 SP9.2
RTD VotingDisabled Enabled or Disabled SP9.3
Stator Phase A1 Type Off
120 OHM NI, 100 OHM NI, 100 OHM PT, 10
OHM CU
RTD #1 DescriptionStator A1 User defined, Up to 15 Characters
Stator Phase A1 Alarm Level Off0-240C (32-464F), Off
Stator Phase A1 Trip Level Off0-240C (32-464F), Off
Stator Phase A2 Type Off Same as Stator Phase A1
RTD #2 DescriptionStator A2 User defined, Up to 15 Characters
Stator Phase A2 AlarmOff 0-240C (32-464F), Off
Stator Phase A2 Trip Level Off0-240C (32-464F), Off
Stator Phase B1 Type Off Same as Stator Phase A1
RTD #3 DescriptionStator B1 User defined, Up to 15 Characters
Stator Phase B1 Alarm Level Off0-240C (32-464F), Off
Stator Phase B1 Trip Level Off0-240C (32-464F), Off
Stator Phase B2 Type Off Same as Stator Phase A1
RTD #4 DescriptionStator B2 User defined, Up to 15 Characters
Stator Phase B2 Alarm Level Off0-240C (32-464F), Off
Stator Phase B2 Trip Level Off0-240C (32-464F), Off
Stator Phase C1 Type Off Same as Stator Phase A1
RTD #5 DescriptionStator C1 User defined, Up to 15 Characters
Stator Phase C1 Alarm Level Off0-240C (32-464F), Off
Stator Phase C1 Trip Level Off0-240C (32-464F), Off
Stator Phase C2 Type Off Same as Stator Phase A1
RTD #6 DescriptionStator C2 User defined, Up to 15 Characters
Stator Phase C2 Alarm Level Off0-240C (32-464F), Off
Stator Phase C2 Trip Level Off0-240C (32-464F), Off
End Bearing Type Off Same as Stator A1
RTD #7 Description End Bearing User defined, Up to 15 Characters
End Bearing Alarm Level Off0-240C (32-464F), Off
End Bearing Trip Level Off0-240C (32-464F), Off
Shaft Bearing Type Off Same as Stator Phase A1
RTD #8 Description Shaft Bearing User defined, Up to 15 Characters
Shaft Bearing Alarm Level Off0-240C (32-464F), Off
Shaft Bearing Trip Level Off0-240C (32-464F), Off
RTD #9 Type Off Same as Stator Phase A1
RTD #9 Description User defined User defined, Up to 15 Characters
RTD #9 Alarm Level Off0-240C (32-464F), Off
RTD #9 Trip Level Off0-240C (32-464F), Off
Page 9
RTD Configuration
Level 3
Password Protection
SP9.4