5.1.3PhaseandGroundSettings(SetpointPage3)
* Ground fault option must be installed.
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Imbalance Alarm Level 15% FLA 5-30 %, Off
Imbalance Alarm Delay 1.5 sec 1.0-20.0 sec
Imbalance Trip Level 20% 5-30 %, Off
Imbalance Trip Delay 2.0 sec 1.0-20.0 sec
Undercurrent Alarm Level Off 10-90 %, Off
Undercurrent Alarm Delay 2.0 sec 1.0-60.0 sec
Overcurrent Alarm Level Off 100-300 %, Off
Overcurrent Alarm Delay 2.0 sec 1.0-20.0 sec
Overcurrent Trip Level Off 100-300 %, Off
Overcurrent Trip Delay 2.0 sec 1.0-20.0 sec
Phase Loss Trip Enabled Enabled or Disabled
Phase Loss Trip Delay 0.1 sec 0-20.0 sec
Phase Rotation Detection ABC ABC, ACB or Disabled
Phase Rotation Trip Delay 1.0 sec 1.0 - 20.0 sec
*Ground Fault Alarm Level Off5-90 %, Off
*Ground Fault Alarm Delay 0.1 sec 0.1-20.0 sec
*Ground Fault Loset Trip Level Off5-90 %, Off
*Ground Fault Loset Trip Delay 0.5 sec 0.1-20 sec
*Ground Fault Hiset Trip Level Off5-90 %, Off
*Ground Fault Hiset Trip Delay 0.008 sec 0.008-0.250 sec
Overvoltage Alarm Level Off5 -30%, Off
Overvoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Overvoltage Trip Level 10% 5-30%, Off
Overvoltage Trip Delay 2.0 sec 1.0-30.0 sec
Undervoltage Alarm Level Off5-30%, Off
Undervoltage Alarm Delay 1.0 sec 1.0-30.0 sec
Undervoltage Trip Level 15% 5-30%, Off
Undervoltage Trip Delay 2.0 sec 1.0-30.0 sec
Line Frequency Trip Window Disabled 0-6 Hz, Disabled
Line Frequency Trip Delay 1.0 sec 1.0-20.0 sec
P/F Lead P/F AlarmOff 0.1-1.00, Off
P/F Lead Alarm Delay 1.0 sec 1-120 sec
P/F Lead P/F Trip Off.01-1.00, Off
P/F Lead Trip Delay 1.0 sec 1-120 sec
P/F Lag P/F AlarmOff .01-1.00, Off
P/F Lag Alarm Delay 1.0 sec 1-120 sec
P/F Lag P/F Trip Off.01-1.00, Off
P/F Lag Trip Delay 1.0 sec 1-120 sec
Power Demand Period 10 min1 - 60 min
KW Demand Alarm Pickup Off KW Off, 1-100000
KVA Demand Alarm Pickup Off KVA Off, 1-100000
KVAR Demand Alarm Pickup Off KVAR Off, 1-100000
Amps Demand Alarm Pickup Off Amps Off, 1-100000
Page 3
Phase and Ground Settings
Level 2
Password Protection
SP3.1
SP3.2
SP3.3
SP3.4
SP3.5
SP3.6
SP3.7
SP3.8
SP3.11
SP3.12
SP3.18
SP3.20
SP3.13
SP3.14
SP3.15
SP3.9
SP3.10
SP3.19
SP3.17
SP3.16