SP.6UserI/OConguration(SetpointPage6)
(SecurityLevel:2)
: The
controller provides up to 4 digital external inputs
which are individually programmable. A description
name can be assigned to each individual input for
easy identication.
 Factory programmed for TCB
Trip.
  If used, this setpoint must be
enabled.
 The user can assign a
description name to the input to easily identify
the cause of external trip or alarm. Up to 15
characters including spaces can be used to assign
the name.
 The external input can
be set as either a normally open or normally
closed contact.
  Upon a change in
contact setting, the unit will wait the programmed
amount of time before generating an output. If
no delay is needed, then input 0 seconds. The
controller will post an event upon seeing a change
in state.
 : The setup screens and
setpoints for External Input #3 includes the option
of being congured for Dual Ramp. In Dual Ramp
mode, the initial contact setting is the same as the
START RAMP #1. Upon a change in input contact
state, the controller will switch over to START
RAMP #2 and use that setting for start control
mode. Note: The start RAMP types should only be
switched while the motor is stopped. In Setpoint
Page 4 Relay Assignments, do not assign any
output relay to this function. The controller will
ship with External input #3 programmed for dual
ramp. If it is not needed, disable the dual ramp.
 : This input screens are for the
thermostat input and can be enabled or disabled.
Note: It is recommended that this function remain
enabled. If the thermostat indicates an over
temperature condition, the controller will trip the
motor.
USER
PROGRAMMABLE
EXTERNAL
INPUTS
(Continued)
TCB FAULT
SELECT: ENABLED
NAME EXT. INPUT #1
TCB FAULT
Options: Enabled or Disabled See text for directions
EXTERNAL INPUT #2
SELECT: DISABLED
NAME EXT INPUT #2
Options: Enabled or Disabled See text for directions
DUAL RAMP
SELECT: DUAL RAMP
NAME EXT INPUT #3
SECOND RAMP
Options: Enabled, Disabled or
Dual Ramp
See text for directions
THERMOSTAT
SELECT: ENABLED
NAME EXT INPUT #4
THERMOSTAT
Options: Enabled or Disabled See text for directions
TCB FAULT
TYPE: NORMALLY OPEN
Options: Normally Open or
Normally Closed
EXTERNAL INPUT #2
TYPE: NORMALLY OPEN
Options: Normally Open or
Normally Closed
DUAL RAMP
TYPE: NORMALLY OPEN
Options: Normally Open or
Normally Closed
THERMOSTAT
TYPE: NORMALLY CLOSED
Options: Normally Open or
Normally Closed
TCB FAULT
TIME DELAY: 1 SEC.
Range: 0 - 60 SEC
Increments of 1
EXTERNAL INPUT #2
TIME DELAY: 0 SEC.
Range: 0 - 60 SEC.
Increments of 1
DUAL RAMP
TIME DELAY: 0 SEC.
Range: 0 - 60 SEC
Increments of 1
THERMOSTAT
TIME DELAY: 1 SEC.
Range: 0 - 60 SEC.
Increments of 1