Toshiba VF010H05 Remote Starter User Manual


 
JKSSS+ Series - 36
JKSSS+ Series 2.3 - 4.2KV
5.1 SetpointsPageList
These charts list the Setpoint Page, the programmable functions and the section.
5.1.1BasicConguration(SetpointPage1)
5.1.2StarterConguration(SetpointPage2)

The JKSSS+ Series has thirteen programmable setpoint pages which dene the
motor data, ramp curves, protection, I/O conguration and communications. In Section
5.1, the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages
are illustrated and dened for easy navigation and programming. Note: Setpoints can
only be changed when the starter is in the Ready Mode. Also the soft start will not start
when it is in programming mode.
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Start Control Mode Start Ramp 1
Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp,
Tach Ramp
SP2.1
Jog Voltage 50% 5-75%, Off
SP2.2
Start Ramp #1 Type Voltage Current, Voltage
Initial Voltage #1 20% 0-100%
Ramp Time #1 10 sec 0-120 sec
Current Limit #1 350% FLA 200-500 %
Initial Current #1 200% FLA 0-300%
Ramp Time #1 10 sec 0-120 sec
Maximum Current #1 350% FLA 200-500 %
Start Ramp #2 Type Disabled Current, Voltage, Disabled
Initial Voltage #2 60% 0-100 %
Ramp Time #2 10 sec 0-120 sec
Current Limit #2 350 % FLA 200-500 %
Initial Current #2 200% FLA 0-600 %
Ramp Time #2 10 sec 0-120 sec
Maximum Current #2 350% FLA 200-500 %
Kick Start Type Disabled Voltage or Disabled
Kick Start Voltage 65% 10-100 %
Kick Start Time 0.50 sec 0.10-2.00
Deceleration Disabled Enabled or Disabled
Start Deceleration Voltage 60% 0-100 %
Stop Deceleration Voltage 30% 0-59 %
Deceleration Time 5 sec 1-60 sec
Timed Output Time Off1-1000 sec, Off
SP2.7
Run Delay Time 1 Sec 1-30 sec, Off
SP2.8
At Speed Delay Time 1 Sec 1-30 sec, Off
SP2.9
SP2.3
SP2.4
SP2.5
SP2.6
Page 2
Starter Configuration
Level 1
No Passowrd Required
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Motor Full Load Amps (FLA) Model dependent
50 - 100% of Unit Max Current Rating
(Model and Service Factor dependent)
SP1.1
Service Factor 1.15 1.00 – 1.3 SP1.2
Overload Class 10 O/L Class 5-30 SP1.3
NEMA Design BA-F SP1.4
Insulation Class BA, B, C, E, F, H, K, N, S SP1.5
Line Voltage Model dependent 1000 to 7200V SP1.6
Line Frequency 60 50 or 60 HZ SP1.7
Page 1
Basic Configuration
Level 1
No Passowrd Required