Toshiba VF010H05 Remote Starter User Manual


 
JKSSS+ Series - 44
JKSSS+ Series 2.3 - 4.2KV
5.1.12System(SetpointPage12)
5.1.13CalibrationandService(SetpointPage13)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Default Display Screen
Metering Data Page #1 Enter Metering Page (1-4)
Metering Data Screen #1
Enter Metering Screen
Page 1(1-10)
Page 2 (1-11)
Page 3 (1 - 29)
Page 4 (1 - 6)
Alarms
RTD Failure AlarmDisabled Enabled or Disabled
Thermal Register Alarm 90% Off, 40-95%
Thermal Alarm Delay 10 sec 1-20 sec
Thermal Register Setup Info
Cold Stall Time O/L Class O/L Class (5-30) or 4-40 second time delay
Hot Stall Time ½ O/L Class ½ O/L Class, 4-40 sec
Stopped Cool Down Time 30 Min 10-300 Min
Runing Cool Down Time 15 Min 10-300 Min
Relay Measured Cool Rates Disabled Enabled or Disabled
Thermal Register Minimum 15% 10-50%
Motor Design Ambient Temp 40C 10-90C
Motor Design Run Temperature 80% Max 50-100% of Motor Stator Max Temp
Motor Stator Max Temp INS CLS INS CLS, 10-240 C
I/B Input to Thermal Register Enabled Enabled or Disabled
Use Calculated K or Assign 71-50, On
Press Enter to Clr Thermal Register SP12.4
Page 12
System Setpoints
Level 3
Password Protection
SP12.2
SP12.3
SP12.1
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Set Date and Time
(DDMMYY:HHMM)
FACTORY SET;
##/##/## ##:##
Enter Date (DDMMYYYY)
FACTORY SET;
##/##/####
D=1-31, M=1-12, Y=1970-2069
Enter Time (HH:MM)
FACTORY SET;
##:##
H=00-23, M=0-59
Model #
Firmware REV. #
FACTORY SET;
###### ######
Display Only, Cannot be changed SP13.2
Press Enter to Access Factory
Settings
Available to Qualified Factory Personnel SP13.3
Page 13
Calibration & Service
FACTORY USE ONLY
SP13.1