Emerson 3300 Radar Detector User Manual


 
Reference Manual
00809-0100-4811, Rev CA
February 2006
4-23
Rosemount 3300 Series
Setup - LCD The LCD tab lets you specify which parameters to appear on the display
panel. The display has two rows, the upper row with five characters is for the
measured value and the lower row with six characters for the value name.
The display toggles between the different variables every 2 seconds.
Figure 4-18. Setup LCD tab
Choose one of the following options:
Table 4-3. LCD parameters
Parameter Description
Level Product level.
Distance Distance from the upper reference point to the product surface.
Volume Total product volume.
Internal Temperature Temperature inside the transmitter housing.
Interface Distance Distance between the upper reference point and the interface
between the upper and lower product.
Interface Level Level of the lower product.
Interface Thickness Thickness of the upper product.
Amplitude Peak 1 Signal amplitude of the reflected signal from the reference pulse.
Amplitude Peak 2 Signal amplitude of the reflected signal from the product surface.
Amplitude Peak 3 Signal amplitude of the reflected signal from the surface of the
bottom product (interface measurements).
Percent Range Level value in percent of total measurement range.
Analog Output Current 4 -20 mA current.
RCT-SETUP LCD