Emerson 3300 Radar Detector User Manual


 
Reference Manual
00809-0100-4811, Rev CA
February 2006
3-15
Rosemount 3300 Series
Shortening the Probe Flexible Twin/Single Lead
Rigid Single Lead
1. Cut the Single Lead probe to the desired length.
2. Update the transmitter configuration to the new probe length, see “Probe
Length“ on page 4-9.
NOTE!
The PTFE covered probes must not be cut in field.
1. Mark off the required probe length. Add at
least 1.6 inch/40 mm to the required probe
length to be inserted into the weight.
2. Loosen the Allen screws.
3. Slide the weight upwards as much as
needed in order to cut the probe.
4. Cut the probe. If necessary, remove a
spacer to make room for the weight.
5. Slide the weight down to the required
cable length.
6. Tighten the screws.
7. Update the transmitter configuration to the
new probe length, see “Probe Length“ on
page 4-9.
If the weight was removed from the cables
when cutting, make sure that at least 1.6
inch/40 mm of the cable is inserted when the
weight is replaced.
Allen
screws
Minimum:
1.6 inch/
40 mm
Spacer
Cut
FLEX TWIN SHORT3