Emerson 3300 Radar Detector User Manual


 
Reference Manual
00809-0100-4811, Rev CA
February 2006
4-19
Rosemount 3300 Series
Setup - Output The Output tab lets you assign up to four transmitter variables.
Figure 4-15. Setup output tab
Typically, the Primary Variable (PV) is configured to be Product Level,
Interface Level or Volume.
Other variables like Product Distance, Interface Distance, Upper Product
Thickness, etc. are available as well.
For the Rosemount 3301 the primary variable is typically set to be Level. If the
transmitter is in the Immersed Probe mode (see section
Measurement Mode) the PV is normally set to Interface Level.
For the Rosemount 3302 the PV is typically set to Interface Level, but Level
and other options may also be used.
Set the Lower Range Value (4 mA) and the Upper Range Value (20 mA) to
the desired values. Keep in mind that the 20 mA value should be below the
Upper Dead Zone, and the 4 mA point should be above the Lower Dead Zone
if you want to use the full 4-20 mA range within the measuring range of the
transmitter.
Also make sure that the 20 mA value is set below the Upper Null Zone (UNZ).
(the UNZ parameter may be used if there are measurement problems in the
upper part of the tank, see Section 6: Disturbances at the Top of the Tank).
The UNZ is equal to zero in the default configuration.
See Section 2: Dead Zones for more information on Upper and Lower Dead
Zones.
See Section 4: Basic Configuration for more information on setting the Upper
and Lower Range values.
The default Damping value is 10. Normally this value does not need to be
changed. The Damping parameter may be changed if there are high filling
rates, see “High Level Rates” on page 6-7 for more information.
RCT-SETUP_OUTPUT