Rosemount 3300 Series
VOLUME
CONFIGURATION
Transmitter Variables
Select the Volume option in order to configure the transmitter for volume
measurements.
Volume Units
Choose one of the following units:
Gallons
•Liters
Imperial Gallons
Cubic Meters
•Barrels
•Cubic Yards
Cubic Feet
Cubic Inch
Tank Type
Choose a standard tank shape, or select the strapping option. Standard
shapes are: Vertical Cylinder, Horizontal Cylinder, Vertical Bullet, Horizontal
Bullet or Sphere. (If Primary Variable is Level choose None for Tank Type).
If your tank does not correspond to any of the above tank shapes, select Strap
Table.
Tank Dimensions
If a standard tank type was chosen, enter the diameter and height of the tank.
See “Volume Configuration” on page 4-5 for information on how to specify
tank dimensions.
Strapping Table
If tank type Strapping Table was chosen, enter how many entries you will use
and the actual level and volume points. You can enter from 2 to 10 points. The
strapping points must be entered such that the first point corresponds to the
lowest level, and the last point corresponds to the topmost level of the tank.