Reference Manual
00809-0100-4811, Rev CA
February 2006
Rosemount 3300 Series
4-22
Measurements Below Probe End
The Present Level=0... check box controls how the level value is presented
when the tank is almost empty. By selecting this check box the Level is set
equal to zero as long as the product surface is below the probe.
If the check box is not selected, the Level value is equal to the difference
between Reference Gauge Height R and Probe Length L when the product
surface is below the probe (see “Basic Configuration” on page 4-2 for
information on tank geometry).
Setup - Volume The Volume tab lets you configure the transmitter for volume calculations.
Figure 4-17. Setup Volume tab
You can choose one of the standard tank shapes or the strapping option.
Choose None if volume calculation is not used at all.
Choose one of the following options:
• Vertical Cylinder
• Horizontal Cylinder
• Vertical Bullet
• Horizontal Bullet
• Sphere
• Strap table
•None
See Section 4: Volume Configuration for more information on Volume
configuration.
Level=0
Level=R-L
LEVELBELOWPROBE.EPS
RCT-SETUP VOLUME