Mitsubishi Electronics WT03939X20 Automobile Accessories User Manual


 
78
The function allotment of DIDO Controller, G(B)-50A Web,TG-2000A and Maintenance Tools is as follows.
[Note]S:Setting possibility, M:Monitoring only, -:None
Function name DIDO Controller G(B)-50A
Web
TG-2000A Maintenance Tools
Address setting S*1 - - M
Output method
(Level/pulse) setting
S*1 - - M
Error input logic (a
contact/b contact) setting
S*1 - - M
Group registration - S S -
Operation and monitoring -
S S M
(Compulsion operation is
possible.)
Time setting - S S M
(Operation is possible)*2
The following settings and monitoring can be made on DIDO Controllers (PAC-YG66DCA).
Set the current time before using the DIDO Controller.
When G(B)-50A or TG-2000A is connected, the time setting must be made on G(B)-50A Web or
TG-2000A.
When neither of them is connected, refer to section [3.13.1.1 Time setting on DIDO Controllers].
(a) Operation
*Contact output
*Operation time reset
(b) Monitoring
*Input/output status
*Operation time (contact ON/OFF hours)
*Dip switch settings
3.13.1.1 Time setting on DIDO Controllers
(1) Click [Option] in the menu bar and
select [DIDO/AI/PI] -> [DIDO setting] in
the sub-menu.
(2) Click of the unit (DIDO Controller)
to be set or monitored on the Main screen.
(3) DIDO controller (66DC) input/output status
monitoring screen will appear.
(4) Click [Date/Time setting] in the
DIDO controller (66DC) input/output status
monitoring screen.
NOTE:
When G(B)-50A or TG-2000A is connected, the time setting must be made on G(B)-50A Web or TG-2000A.
*1 It is set with Dip switch of DIDO Controller.
*2 When G(B)-50A or TG-2000A is connected, the time setting must be made on G(B)-50A Web Browser or TG-2000A.