Mitsubishi Electronics WT03939X20 Automobile Accessories User Manual


 
48
3.10.3 Screen Functions and Operation(BC Controller)
(1) Click on the button corresponding to the valve number
you want to change.
“0” represents “close” and “1” represents “open”.
To change the valve setting, perform
“Fix Release” --> “Fix”
(2) After setting, click on .
(3) Click on to check the current conditions.
(4) Change the LEV opening with . Set to the LEV
opening. Click on to send the setup
contents.
(5) After adjustment by solenoid valve and LEV opening change is complete, click on .
The Main Screen will return. At this time, the contents set at this screen become invalid.
NOTE:
To prevent failure to release the status set after test run, close the operation control screen of
BC/BS controller.
This releases all the content set
on this screen automatically.
However when moving to the operation control screen of BC/BS controller from the operation monitor
screen,
the set content will be retained even by closing this screen
.
At a timing when finishing the operation monitor screen, the set content can be released.