(3) Mountable main base unit, mountable power supply module, number of
mountable modules
Mount the MELSECNET/H remote I/O module on the CPU slot of a main base unit.
(4) Applicable extension base unit
The system including the MELSECNET/H remote I/O module can be extended using extension base units.
*1 Calculate the operating voltage of the extension base unit used and check that the voltage is within the rating.
*2 When using extension cables, pay attention to the following.
Main base unit
Power
supply
module
Number of mountable
MELSECNET/H remote
I/O modules
Remarks
Q33B, Q35B, Q38B, Q312B Q6P
1
Mountable only
on the CPU slot
Q35BL, Q38BL
(Q series large type main base unit)
Q6P
Q35BLS, Q35BLS-D, Q38BLS, Q38BLS-D
(Q series large type main base unit (AnS series size))
Q6P
Q32SB, Q33SB, Q35SB
(Slim type main base unit)
Q61SP
Q35DB, Q38DB, Q312DB
(Multiple CPU high-speed main base unit)
Q6P
Q38RB
(Main base unit for redundant power supply system)
Q63RP, Q64RP
Extension base unit
Extension cable
*2
(Overall cable distance:
13.2m or less)
Number of
extension
base units
Q63B, Q65B, Q68B, Q612B
(Extension base unit (type requiring a power supply module))
QC05B, QC06B, QC12B,
QC30B, QC50B, QC100B
Max. 7
Q52B, Q55B
(Extension base unit (type requiring no power supply module))
*1
Q65BL, Q68BL
(Q series large type extension base unit (type requiring a power
supply module))
Q55BL
(Q series large type extension base unit (type requiring no power
supply module))
*1
Q65BLS, Q65BLS-D, Q68BLS, Q68BLS-D
(Q series large type extension base unit (AnS series size) (type
requiring a power supply module))
Q55BLS, Q55BLS-D
(Q series large type extension base unit (AnS series size) (type
requiring no power supply module))
*1
Q68RB
(Extension base unit for redundant power supply system)
• For the calculation formula, refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection).
• For the current consumption of each module mounted on the extension base unit, refer to the manual for each
module used.
• Do not install extension cables together with the main circuit lines (high voltage and large current).
• Connect a cable between the OUT connector of an extension base unit and the IN connector of the next-level
extension base unit.