98
3001
[PARAMETER ERROR]
The parameter settings are corrupted.
■Collateral information
• Common Information (SD5 to SD15): File name
• Individual Information (SD16 to SD26): Parameter number
■Diagnostic Timing
• At power-on/At reset
*2
• Read the individual information of the error using GX
Works2 or GX Developer to identify the numeric
value (parameter number). Check the parameters
corresponding to the value, and correct them as
necessary.
• Rewrite corrected parameters to the remote I/O
module, reload the power supply of the remote I/O
module and/or reset the module.
If the same error occurs, the cause is a hardware
failure. (Please consult your local Mitsubishi
representative.)
REM: Off
ERR: On
Remote I/O status: Stop
3103
[LINK PARA. ERROR]
• Although one or more Ethernet modules were configured
in the Network Parameter dialog box, no Ethernet module
is mounted in the system.
• The start I/O number of the Ethernet network parameter
differs from that of the actually mounted module.
■Collateral information
• Common Information (SD5 to SD15): File name
• Individual Information (SD16 to SD26): Parameter number
■Diagnostic Timing
• At power-on/At reset
*2
• Correct and write the network parameters.
• If an error occurs again even after it is corrected, the
cause is a hardware failure. (Please consult your
local Mitsubishi representative.)
REM: Off
ERR: On
Remote I/O status: Stop
3104
[LINK PARA. ERROR]
• The network number, station number or group number set
in the network parameter is out of range.
• The specified I/O number is outside the range of the used
remote I/O module.
• The Ethernet-specific parameter settings are incorrect.
■Collateral information
• Common Information (SD5 to SD15): File name
• Individual Information (SD16 to SD26): Parameter number
■Diagnostic Timing
• At power-on/At reset
*2
• Correct and write the network parameters.
• If an error occurs again even after it is corrected, the
cause is a hardware failure. (Please consult your
local Mitsubishi representative.)
REM: Off
ERR: On
Remote I/O status: Stop
3105
[LINK PARA. ERROR]
• Although one or more CC-Link modules were configured in
the Network Parameter dialog box, no CC-Link module is
mounted in the system.
• The start I/O number in the common parameter differs from
that of the actually mounted module.
• The station type of the CC-Link module network parameter
differs from that of the actually mounted station.
■Collateral information
• Common Information (SD5 to SD15): File name
• Individual Information (SD16 to SD26): Parameter number
■Diagnostic Timing
• At power-on/At reset
*2
• Correct and write the network parameters.
• If an error occurs again even after it is corrected, the
cause is a hardware failure. (Please consult your
local Mitsubishi representative.)
REM: Off
ERR: On
Remote I/O status: Stop
3106
[LINK PARA. ERROR]
The network refresh parameter for CC-Link is out of range.
■Collateral information
• Common Information (SD5 to SD15): File name
• Individual Information (SD16 to SD26): Parameter number
■Diagnostic Timing
• At power-on/At reset
*2
Check the parameter setting.
REM: Off
ERR: On
Remote I/O status: Stop
3107
[LINK PARA. ERROR]
• The CC-Link parameter setting is incorrect.
• The set mode is not allowed for the version of the mounted
CC-Link module.
■Collateral information
• Common Information (SD5 to SD15): File name
• Individual Information (SD16 to SD26): Parameter number
■Diagnostic Timing
• At power-on/At reset
*2
Check the parameter setting.
REM: Off
ERR: On
Remote I/O status: Stop
Error
code
(SD0)
Error contents and cause Corrective action
LED status,
Remote I/O operation
status