122
(4) Fuse blown module
No. Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corres-
ponding
CPU
SD1300
Fuse
blown
module
Bit pattern in
units of 16
points,
indicating
the modules
whose fuses
have blown
0: No
blown
fuse
1: Blown
fuse
• The number of an output module whose fuse has blown is stored in the
following bit pattern (in units of 16 points). (If the module numbers are set
by parameter, the parameter-set numbers are stored.)
• The status of the blown fuse of an output module on a remote station is
also detected.
• For a module whose number of output points exceeds 16 points, all bits
corresponding to output module numbers within the number of output
points occupied by the module (in units of 16 points) turn on.
When a 64-point module is mounted on the slot 0, b0 to b3 turn on
when the fuse has blown.
• Not cleared even if the blown fuse is replaced with a new one.
The numbers are cleared by clearing the error.
• The module No. is not cleared even when the output module goes back to
normal.
The number is cleared by clearing the error.
S
(Error)
D9100
QnA
Qn(H)
QnPH
QnPRH
QnU
Rem
SD1301 D9101
SD1302 D9102
SD1303 D9103
SD1304 D9104
SD1305 D9105
SD1306 D9106
SD1307 D9107
SD1308
New
SD1309
to
SD1330
SD1331
B15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
000
1
(YC0)
000 00000000
1
(Y80)
SD1300
00
1
(Y1F0)
0000000000
1
(Y1A)
SD1301 0 0
00
1
(Y1F
B0)
00000000SD1331 0 00
1
(Y1F
30)
0
Indicates a blown fuse.
Ex.