84 Using AMS Device Manager to configure the meter
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
March 2013 3-9000-765 Rev D
AMS Device Manager - Manual Setup
Use the Manual Setup wizard to configure the meter’s parameters. See Figure 4-3 and Figure 4-4
and from the AMS Device Manager Configure menu click
Manual Setup.
Figure 4-8 AMS Device Manager - Configure Manual Setup
Procedure
1. If installed, remove security wires from the endcap and the Bracket/Cover hex head
bo
lts that secures the Base Enclosure.
1. Disable the Write Protect switch in the CP
U Module to write any of the following
configuration parameters to your meter.
2. Click the
Device Variables Mapping tab. The Primary and Secondary variables are read
only and are configured for Uncorrected Flow Rate. The Third and Fourth variable
configuration choices include Pressure and Temperature.
3. Click the
Units tab (see AMS Device Manager - Guided Setup, Step 1).
4. Click the Analog Output 1 (HART) tab (see AMS Device Manager - Guided Setup, Step
2a.).
5. Click the
Analog Output 2 tab. Follow the configuration instructions in the AMS Device
Manager - Guided Setup, Step 2b. The read only Secondary variable Content,
Uncorrected Flow Rate, displays. Use the drop-down arrow and select the (flow)
Direc
tion - Forward or Reverse. Enter a Lower and Upper Range limit. Set the Alarm
Action parameters. Click
Apply, after you enter the data to write the parameters to the
meter.
6. Click the
Frequency/Digital Outputs tab. Follow the configuration instructions in the
AMS Device Manager - Guided Setup, Step 3 a.). (Re
fresh Note: If changes are made to
any Source variable on this page, apply the changes and navigate to the Guided Setup