94 Using a Field Communicator to configure the meter
Section 4: Configuration Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
March 2013 3-9000-765 Rev D
Procedure
1. Remove electrical power to the meter. If installed, remove the endcap security latches
and seals and then, remove the endcap.
2. Refer to the Field Communicator Users Manual wiring diagrams and commissioning
in
structions provided with your handheld device. Register the product to activate the
end user license.
3. Fully charge the Field Communicator battery prior to use. Imp
ortant: Do not change
the battery in a hazardous area environment. The power supply is not intrinsically safe.
4. On the meter, run the wires through the field wiring conduit and into the transmitter
el
ectronics enclosure.
Figure 4-19 3812 transmitter field wiring conduit entries
A. Field wiring conduit entries (4)
A.