Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
March 2013 3-9000-765 Rev D
3.6.2 Analog input settings
The 960-24™ MSTS has the capability to sample analog temperature (Analog Input 1) and
pressure (Analog Input 2) with 4-20 mA signals. These analog input sign
als are configured to
sink. The two independent analog input circuits are configured for conventional 4-20 mA
service. Also, 24VDC isolated power supply connection is provided for an external power source.
Refer to the Field wiring diagram (see Appendix A drawing DMC004936).
3.6.3 Analog output settings
The 960-24™ MSTS provides two 4-20 mA analog output signals that are software configurable
for either sink or source current (see Appendix A drawing DMC004936).
Full HART® functionality is provided so that an
y commercially available HART® transmitter
which meets the specifications of the HART® Communications Foundation can be connected to
the Daniel 3812 Liquid Ultrasonic Flow Meter.
Analog Output 2 (AO2) is user-configurable
as a conventional 4-20 mA output.
3.6.4 Digital Input
The Daniel 3812 Liquid Ultrasonic Flow Meter provides one digital input that can be used as a
general purpose input or used for synchronizing calibration (for flow calibration gating - contact
closure). The meter records the volume seen between switch closures. The polarity of the input
is configured as normal or inverted polarity.
pol
arity is determined by the IsDI1ForCalActiveLow and the gating edge is determined by
the IsDI1ForCalStateGated (calibrate edge gated or calibrate state gated).
calibra
tion is started and stopped via an inactive>active state change.
The digital input must be configured via the Daniel MeterLink T
ools>Edit/Compare
Configuration page.
3.6.5 DHCP server switch settings
The meter can be configured to act as a DHCP server. The DHCP server is enabled/disabled via
CPU Module DHCP switch as follows:
Table 3-6 DHCP server switch settings
CPU Module switch DHCP server disabled DHCP server enabled
DHCP OFF ON