Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual Section 3: Electrical installation
3-9000-765 Rev D March 2013
Configuration protect switch settings 61
3.6.6 Configuration protect switch settings
The meter’s configuration parameters and firmware can be protected against changes via CPU
Module Write PROT. switch as follows:
A complete list of write-protected parameters are in Appendix A.
3.6.7 External power source connection and fuse
Located inside the Transmitter Electronics Enclosure is a connector for a user-provided external
power source, a 2 Ampere fuse and a 24V loop power connection for ultrasonic meter analog
outputs, generator transmitter or pressure transmitter devices. The current is limited to 88mA.
Figure 3-7 CPU Module power source connections
Table 3-7 Configuration protect switch settings
CPU Module switch Configuration protected Configuration unprotected
WRITE PROT. ON (default) OFF
A.
B.
A. Power In connector (main power)
B. 24V LOOP POWER
C. 2 Ampere fuse (used for the main power input)
C.