Emerson 3812 Automobile Parts User Manual


 
16 Meter specifications
Section 1: Introduction Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
March 2013 3-9000-765 Rev D
Communications specifications
Connectivity protocols One serial RS-232/RS-485 port (115 kbps baud rate) (Modbus RTU/ASCII)
(1) Serial Port A
(RS-232/RS-485 Full Duplex/RS-485 Half Duplex)
One Ethernet Port (TCP/IP) 100 BaseT
Modbus TCP
Device compatibility
FloBoss 103, FloBoss S600 flow computer, ROC 107
Digital, analog, and frequency inputs
Digital Input(s)
(Selectable)
(1) Single polarity (for flow calibration gating - contact closure)
Single input for starting and stopping
Four pulse configurations available
Analog Input(s) (2) 4-20 mA
AI-1 Temperature
AI-2 Pressure
Note: The analog-to-digital conversion accuracy is within ±0.05% of full scale over the operating
temperature range.
Note: AI
-1 and AI-2 are electronically isolated and operate in sink mode. The input contains a
series resistance so HART® Communicators can be connected to configure sensors.
A 24 Volt DC power supply is available to provide power to the sensors.
Table 1-2 Meter specifications