Section 3: Electrical installation Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
March 2013 3-9000-765 Rev D
3.6.1 Frequency/Digital outputs
The meter has three user-configurable selections for configuring either a Frequency output or
Digital output (FODO).
• F
ODO1 (four possible parameter configurations)
• F
ODO2 (eight possible parameter configurations)
• F
ODO3 (eight possible parameter configurations)
Frequency or Digital Outputs (FODO 1) source
• FO1A, DO1A, FO1B, DO1B
• F
requency output 1A is based on frequency content (Actual - Uncorrected Flow Rate)
• F
requency output 1B is based on frequency content and Frequency 1 B Phase
• Digital
output 1A is based on Digital output1A content (Frequency1A Validity and Flow
Direction)
Frequency or Digital Outputs (FODO 2) source
• FO1A, DO1A, FO1B, DO1B, FO2A, DO2A, FO2B, DO2B
• F
requency output 1A is based on frequency content (Actual - Uncorrected Flow Rate)
• F
requency output 1B is based on frequency content and Frequency 1B Phase
• F
requency output 2A is based on frequency content (Actual - Uncorrected Flow Rate)
• F
requency output 2B is based on frequency content and Frequency 2B Phase
• Digital
output 1A is based on Digital output1A content (Frequency 1A Validity and Flow
Direction)
• Digital
output 2A is based on Digital output2A content (Frequency 1A Validity and Flow
Direction)
• Digital
output 2A is based on Digital output 2A content (Frequency 2A Validity and Flow
Direction)
• Digital
output 2B is based on Digital output 2B content (Frequency 2B Validity and Flow
Direction)