8.2.23 Flow Rate High/Low Alarm and High-High/Low-Low Alarm
The high/low limit, high-high/low-low limit of the flow rate, at which an alarm is generated, can be set
as % value of the span flow rate of the set maximum range.
The high/low alarm, and high-high/low-low alarm values for flow rate can be set within the range of
10% to 110% (percentage to Range 1) in increments of 0.1%.
Changing the high/low alarm on/off setting
The following is an example to change the high alarm setting from OFF to ON.
Switch operation
Display example
Description
Select "H SET" from the setting item
selection menu.
The current setting (OFF in this example)
appears.
Then push .
* Pushing returns you to the menu
screen.