Switch operation
Display example
Description
Pushing when the cursor is positioned
on the 7th character shows a message to
confirm whether the setting is OK or not.
If OK, push . If you want to redo the
setting, push .
Pushing cancels the setting operation
and exits the setting screen.
Note : The selectable characters are displayed cyclically as shown below:
Symbol 1
Numeric
characters
Symbol 1
Alphabetical
characters
(uppercase)
Alphabetical
characters
(lowercase)
Special
character
Space
8.2.9 Span (Range)
You can set the following constants in this setting item:
(1) Range type
(2) Unit of span (can be changed in Range 1)
(3) Span
(4) Hysteresis
Range type
Multiple ranges can be used by selecting the range type. You can select a single range,
multiple ranges, or forward/reverse multiple ranges.
Select one from five types shown below:
Selection items (display) Description
SINGLE Single range
4F-0R
Unidirectional flow,
automatic selection of multiple ranges
2F-2R
Bidirectional flows,
automatic selection of multiple ranges
EXT 2F-0R
Unidirectional flow,
multiple ranges selected by external signa
l
EXT 2F-2R
Bidirectional flows,
multiple ranges selected by external signa
l