Trane X39640516-01 Automobile Parts User Manual


 
52 CLCH-IM-16A
representative for motor lubrication
recommendations.
q Inspect electrical connections. They should be
clean and secure. Compare actual wiring with
specific diagrams on the unit.
q Check piping and valve for leaks. Open or close
the valves to check operation. Drain lines should
be open.
q If unit has a refrigerant coil, it must be charged,
leak-tested, and ready for operation according to
instructions provided with the condenser
equipment. Adjust superheat setting.
q Check that air filters are in place and positioned
properly.
q Remove all foreign material from the drain pan
and check pan opening and condensate line for
obstructions.
q Check unit for debris.
q Close and secure all unit access doors.