Trane X39640516-01 Automobile Parts User Manual


 
22 CLCH-IM-16A
Component Installation Requirements
The T-Series Climate Changer is extremely versatile
and the assembled unit is a complete air handling
system. Each section may have installation
requirements that will affect the performance of the
unit.
High Efficiency Bag and Cartridge Filter Section
The Bag and Cartridge Filter sections can be used as
either a pre-filter section, a Final Filter section or
both. This is determined by placement in relation to
the fan.
Filter Installation
NOTE: CARTRIDGE AND BAG FILTERS PROVIDED BY
TRANE ARE FITTED WITH A 7/8” HEADER THAT FITS
IN THE FILTER TRACK. IF USING FILTERS SUPPLIED
BY ANOTHER MANUFACTURER, FILTERS SHOULD
BE PURCHASED WITH A 7/8” HEADER. IN SOME
CASES IT MAY BE NECESSARY TO GASKET THE
LOCALLY PURCHASED FILTERS TO INSURE A GOOD
AIR SEAL.
FILTERS SHOULD BE INSTALLED WHEN THE UNIT IS
SET. THIS WILL PROTECT INTERNAL COMPONENTS
SUCH AS THE UNIT’S HEATING AND COOLING COILS.
Trane recommends the use of disposable pre-filters
with high efficiency filters. Disposable pre-filters slide
into the mounting tracks just ahead of the bag/
cartridge filters.
WARNING
Pressurized Cabinet!
Disconnect all electric power
before opening door. Failure to
disconnect power before servicing
can cause severe personal injury.
1 Disconnect the power to the unit.
2 Open the filter section access door.
3 Remove the adjustable block-off from the filter
track.
4 Slide the filters into the tracks. Note that bag filters
must be installed with the pleats in the vertical
plane.
5 Slide the adjustable block-offs into the filter track.
The block-off is intended to make a seal when the
access door is closed. It is adjustable and may
require a few changes to insure a proper seal.
6 Close the access door and confirm that there is a
good seal of the filter track block-off against the
access door.
Fan Section
The Fan section can be configured as either draw-
thru or blow-thru. Review the submittals and unit
tagging prior to assembly.
The fan and motor assembly are internally isolated.
The fan and motor bases are bolted to four spring
isolators (see
Figure 19
). The isolators are secured
to the fan section support base. Four (4) shipping tie-
downs are bolted adjacent to the isolators between
the fan isolation base and the support frame.
The shipping tie-downs secure the isolation base to
the support assembly to prevent any damage to the
fan section during shipment of the air handler. The
shipping spacers must be removed prior to unit
operation unless the unit is to be externally isolated.