Outback Power Systems MX60 Automobile Battery Charger User Manual


 
36
Use the <-DAY> and <+DAY> soft keys to preset
the interval day to initiate an automatic equalization
cycle. The EQ INTERVAL displays the number of days
in the interval between cycles and COUNT displays
how many days of the interval have passed.
COUNT EQ INTERVAL
00 000
EXIT -DAY +DAY
Auto Mode initiates when a preset interval day (1-250 days) is reached.
• The default equalize interval (EQ INTERVAL) setting is 000 day leaving the Auto EQ disabled.
• “EQ-MPPT” display indicates the MX60 is trying to reach the target equalize set point.
• The equalize time “EQ 0:00” in Hours:Minutes displays after the equalize set point is reached.
• An incomplete equalization cycle continues into the next day unless the MX60 is powered o or
manually stopped. The remaining EQ time can be viewed in the Log2 Menu.
• The COUNT value will be cleared to 000 when an EQ is started, manually stopped, or MX60 has been
powered o .
• After recharging, an EQ DONE message displayed and a Float cycle begins. To view the MAIN EQ
screens, press the #1 soft key.
To view the MAIN EQ screens, press the #1 soft key.
Auto Mode