Appendix A: Commissioning Checklist
March 2015
Commissioning Checklist
A.1.4 Electrical installation
Completed Not completed
Power supply within limits
YES NO
Voltage measured at the terminal at the
transmitter:
Groundings according to manual and local
regulations
YES NO
Ground check done with multimeter
YES NO
Voltage measured between - terminal and ground:
YES NO
Voltage measured between + terminal and ground:
YES NO
Resistance measured between transmitter head
external ground terminal and tank ground
terminal:
YES NO
Is the cable shield connected according to
guidelines in the Reference Manual and local
regulations?
YES NO
Is the transmitter head external ground terminal
connected according to guidelines in the Reference
Manual and to local regulations?
YES NO
Type and size of cable used for the communication:
Is the lid to the terminal compartment properly
closed?
YES NO
Is the product’s Ex classification in accordance with
requirements?
YES NO