Section 4: Verification Procedure with Fluid
March 2015
Verification Procedure with Fluid
4.3 Transmitter diagnostics review
Verify that no errors or unattended warnings are present.
Figure 4-6. The Diagnostics Window in RRM
To view Diagnostics in RRM, select Tools > Diagnostics.
For more information, see Section Diagnostics in the Rosemount 5300 Series Reference Manual
(document number 00809-0100-4530)
4.4 Monitor level while emptying
During Step 1, the current level/interface reading was verified correct. This step verifies that the
transmitter correctly tracks the surface during the emptying of the tank.
Begin by activating log functionality for the transmitter level/interface output. Either the
DCS-trend or a standalone tool can be used.
In RRM, select Tools > Log.