Emerson 5300 Radar Detector User Manual


 
5
Reference Manual
00809-1600-4530, Rev AA
Section 2: Installation & configuration
March 2015
Installation and Configuration
AI block (FOUNDATION fieldbus). A minimum of four parameters are required to
configure the AI Block.
Channel - Corresponds to the desired sensor measurement
L_TYPE - Defines the relationship to the desired output of the AI Block. Direct or
indirect root.
XD_SCALE - Include 0%, 100%, and engineering units
OUT_SCALE - Include 0%, 100%, and engineering units
For more information, see Section 5.9 F
OUNDATION fieldbus Overview and Appendix E Level
Transducer block in the Rosemount 5300 Series Reference Manual (document number
00809-0100-4530).
2.2.2 Basic configuration using Rosemount Radar Master (RRM)
1. Start the Guided Setup.
2. Start the Configuration Wizard.
3. Select the Device specific setup to see if any additional configuration is needed.
4. Restart the Device.
5. Run Verify level.
6. Select Archive Device to make a complete backup of the device, including several logs,
and echo curves.
7. View live values from the device.
For more information, see Section 5.6 in the Rosemount 5300 Series Reference Manual
(document number 00809-0100-4530).