Section 5: Additional Options
March 2015
Additional Options
In Rosemount Radar Master:
1. Connect to the device.
2. Right click on the device and select Properties.
3. If “Diagnostics Suite” is mentioned in the Device Software Configuration 2 list, the
device supports Signal Quality Metrics.
In a Field Communicator, if SQM is supported, it can be found with the [3, 2, 2, 1]
sequence. Check if “Diagnostics Suite” is present.
SQM can be enabled/disabled in Rosemount Radar Master. Select Setup > Advanced and select
the Signal Quality Metrics tab.
Note
If SQM is not supported or disabled, the signal quality and surface/noise margin will always be
set to 0.
5.3 Verification reflector
The reflector, which is available with single lead flexible probes, is used to test and continuously
verify that the transmitter functions properly in both tank and chamber/pipe installations.
Compared to traditional diagnostics that only monitor the transmitter electronics, the reflector
can also be used to diagnose the upper parts of the probe inside the tank for example build-up,
corrosion monitoring, and other process related conditions.
The primary use-cases for the reflector are:
Verification of transmitter and probe (proof-testing)
High level supervision (continuous monitoring of high level condition)
Figure 5-1. Verification Reflector