Section 2: Installation & configuration
March 2015
Installation and Configuration
To view the analog output signal, select the Tools > Device Display option and select the
Analog Out tab:
Figure 2-5. Presentation of Analog Output Value in Rosemount Radar Master
For more information, see Section Viewing Measurement Data In Rosemount Radar Master in
the Rosemount 5300 Series Reference Manual (document number 00809-0100-4530).
2.4.2 Verify analog output (HART devices only)
Ensure the loop is set to manual mode in the Distributed Control System (DCS) for the
applicable transmitter.
Use the transmitter’s built-in simulation mode to test the analog output settings. Output at
least one arbitrary level or interface and verify that the readings in the DCS match up.
In Rosemount Radar Master, select Tools > Simulation Mode.
Figure 2-6. Simulation Mode