Emerson 5300 Radar Detector User Manual


 
22
Reference Manual
00809-1600-4530, Rev AA
Section 3: Verification and Validation of GWR without Fluid
March 2015
Verification and Validation of GWR without Fluid
Tag#______________________ Serial#___________________________
Parameter
Initial
Value
Current
value
Tolerance
Within
tolerance?
(Yes or No)
Date
Temperature of chamber
LRV (4 mA setting)
URV (20 mA setting)
Reference peak Amplitude ± 10%
(1)
(1) Normal variation of peak amplitude is ± 10% and depends on the ambient temperature. If the initial measurement was performed in one extreme temperature and
the validation measurement is performed at the other extreme, the amplitude can differ by as much as 20%.
Reference peak Zero point position ±1 mm
Seal pulse peaks
Peak 1 Amplitude ±10%
(1)
Position ± 5 mm
Peak 2 Amplitude ±10%
(1)
Position ± 5 mm
Peak 3 Amplitude ± 10%
(1)
Position ± 5 mm
Noise floor General amplitude 500 mV below
surface threshold
Noise floor Distinctive peak 1: distance
Amplitude 500 mV below
surface threshold
Distinctive peak 2: distance
Amplitude 500 mV below
surface threshold
End of probe peak Direction
End of probe peak Distance
±0.12 in. (3 mm) or
0.03% of measured
distance, whichever is
greatest
(2)
(2) Ambient temperature effect ± 0.008 in. (0.2 mm) /K or ± 30 ppm/K of measured value, whichever is greatest.
End of probe peak Amplitude ± 10%
(1)
Verification reflector Distance ±0.12 in. (3 mm) or
0.03% of measured
distance, whichever is
greatest
(2)
Verification reflector Amplitude ±10%
(1)
Verification reflector mA Output