Section 3: Verification and Validation of GWR without Fluid
March 2015
Verification and Validation of GWR without Fluid
a. Reference pulse amplitude and location with regard to the zero line
(see Table 3-1)
Reference pulse amplitude varies with the type of probe used and the size of the
chamber.
Table 3-1. Reference Peak Examples
Single probe,
standard
Single probe,
HTHP
Coaxial
Standard
Coaxial HTHP Twin Standard DVC probe
Amplitude
1200-16000 mV
Amplitude
9000-11000 mV
Amplitude
5000-7000 mV
Amplitude
5000-7000 mV
Amplitude
9000-11000 mV
Amplitude
8000-11000 mV