Barnett Engineering CV2 Automobile Alarm User Manual


 
Configuration using the PC 4-16
B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2
Level 2 When the incoming call is answered by the Cv2, only the Site ID is
announced; for further access to the Cv2 the caller must enter the Access
Code.
Level 3 An incoming call results in the Cv2 coming off-hook with no
announcement; the Access Code must be entered within ten seconds or the
Cv2 will hang up.
Default Security Level: Level 1
Access Code
An Access Code is needed when calling into a unit configured for security levels 2 or 3.
If the Access Code is empty, all incoming callers will be permitted access to the
program mode. If a code is programmed, it must be entered for remote programming
otherwise the incoming call will be terminated. Local programming is always
accessible.
This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits
including A, B, C, and D.
Default Access Code: an empty string.
Shift Change Code
The shift that is being used at any particular time is determined by the last time that a Shift
Change Code message was received. The Cv2 retains the current shift when it is powered
down and returns to that shift when power is restored. Each time a Shift Change Code is
received, the shift advances by one. If the Cv2 is currently set to shift 4 and the change
code is received, it will go to the shift 1 setting.
This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including
A, B, C, and D.
Default Shift Change Code: an empty string.
Temporary Acknowledge Time
Temporary Acknowledge time is used as a safeguard with the Acknowledge Code. When
the Temporary Acknowledge Time is set to Off it has no effect on Cv2 operations.
Normally, receipt of the Acknowledge Code for a group will cause that group to cease
alarm reporting activities until a new alarm is detected. When this control is set to any of
the four available times (30, 60, 120 and 240 minutes), receipt of the Acknowledge Code,
with the digit ‘#’ appended to it, will cause the alarm activities to cease only for the time
period set by the Temporary Time. After this timer expires, if the alarm condition has not
been removed, the Cv2 will continue alarm functions as though the Acknowledge Code had
not been received.
Default Temporary Acknowledge Time: Off
Call Progress
When Call Progress is enabled, the Cv2 will wait for the called party to speak before
beginning the voice announcement. When Call Progress is enabled, there should not be
any Answer commands directly following a Dial command in the directories. This will
cause the Cv2 to look for a voice response twice in a row and may prevent alarm
announcements.
Default Call Progress: disabled