Barnett Engineering CV2 Automobile Alarm User Manual


 
Operations Overview 2-9
B1272M001
BARNETT ENGINEERING LTD. ProTalk Cv2
Are the inputs connected properly?
For digital inputs that are programmed for standard digital operation, create an alarm
condition on the input and confirm that the Alarm LED comes on. Make sure the input is
applied long enough for the debounce to time out. If the Alarm indicator does not come on,
the problem is not necessarily with the input connection. Check that the input is enabled as a
valid point, the associated group is enabled, and the directory is programmed to call out..
For analog inputs (Advanced mode only), interrogate their group to hear the scaled value at
the input.
The unit does not dial out.
Check the Alarm LED to confirm that an alarm is present. If this indicator is not flashing, the
Cv2 will not call out. For Advanced mode programming, check that the input is enabled as a
valid point, the associated group is enabled, and the directory is programmed to call out. For
Basic mode programming, check that the alarm has a valid directory selected.
I cannot call into the unit.
If you receive a recording from the telephone company indicating the user is not available,
there may be a problem with the installation or you may be calling the wrong number. Use
the programming phone to confirm the telephone number in the unit.