Baldor MN894 Remote Starter User Manual


 
2-2 Installation MN894
Table 2-1 Three Phase
Rating
Fuse MCP (GE)
R
a
ti
ng
(AMPS)
Amps Class
Short Circuit
A
RMS
Amps Type
Short Circuit
A
RMS
8 100 J 5,000 20 5,000
16 100 J 5,000 20 5,000
30 200 J 5,000 50 5,000
100 RK1 5,000 50
SELA
,
55 175 J 42,000 100
SELA
SFLA
10,000
80 175 J 42,000 100
SFLA
SGLA
10,000
160 400 RK5 100,000 300
SGLA
SKLA
42,000
250 400 RK5 100,000 300
SKLA
42,000
420 800 L 100,000 600 42,000
600 800 L 100,000 600 42,000
840 1200 L 100,000 600 42,000
Note: Maximum recommended fuses/breakers are based on 25°C ambient, maximum continuous current.
Figure 2-4 Multipurpose Control Terminal Locations
T1 T2 T3
L1 L2 L3
(A) Line Input
(A) Motor Output Load
(C) Control Connections
(D) GND
(D) GND