Mitsubishi Electronics FR-F740EC/E1 Automobile Accessories User Manual


 
24
MITSUBISHI ELECTRIC
FR-F 740 EC/E1
130
PID integral time
0.1–3600 s / 9999 1 s
131
PID upper limit
0–100% / 9999 9999
132
PID lower limit
0–100% / 9999 9999
133
PID action set point
0–100% 0%
134
PID differential time
0.01–10.00 s / 9999 9999
135
Power-supply switchover sequence output terminal selection
0/1 0
136
MC switchover interlock time
0–100 s 1 s
137
Waiting time at a start
0–100 s 0.5 s
138
Commercial power-supply operation switchover selection at an
alarm
0/1 0
139
Automatic switchover frequency between inverter and commercial
power-supply operation
0–60 Hz / 9999 9999
140
Backlash acceleration stopping frequency
0–400 Hz 1 Hz
141
Backlash acceleration stopping time
0–360 s 0.5 s
142
Backlash deceleration stopping frequency
0–400 Hz 1 Hz
143
Backlash deceleration stopping time
0–360 s 0.5 s
144
Speed setting switchover
0 / 2 / 4 / 6 / 8 / 10 / 102 / 104 /106 / 108 / 110 4
145
PU display language selection
0–7 1
148
Stall prevention level at 0 V input
0–120% 110%
149
Stall prevention level at 10 V input
0–120% 120%
150
Output current detection level
0–120% 110%
151
Output current detection signal delay time
0–10 s 0 s
152
Zero current detection level
0–200% 5%
153
Zero current detection time
0–1 s 0,5 s
154
Voltage reduction selection during stall prevention operation
0/1 1
155
RT signal reflection time selection
0/10 0
156
Stall prevention operation selection
0–31 / 100 / 101 0
157
OL signal output timer
0–25 s / 9999 0
158
AM terminal function selection
1–3/5/6/8–14/17/21/24/50/52/53
1
159
Automatic switchover ON range between commercial power-sup
-
ply and inverter operation
0–10 Hz / 9999 9999
160
User group read selection
0 / 1 / 9999 9999
161
Frequency setting/key lock operation selection
0/1/10/11 0
162
Automatic restart after instantaneous power failure selection
0/1/10/11 0
163
First cushion time for restart
0–20 s 0 s
164
First cushion voltage for restart
0–100% 0%
165
Stall prevention operation level for restart
0–120% 110%
166
Output current detection signal retention time
0–10 s / 9999 0.1 s
167
Output current detection operation selection
0/1 0
168
Parameter for manufacturer setting. Do not make setting!
——
169
170
Cumulative power meter clear
0 / 10 / 9999 9999
171
Operation hour meter clear
0 / 9999 9999
172
User group registered display/batch clear
9999 (0–16) 0
173
User group registration
0–999 / 9999 9999
174
User group clear
0–999 / 9999 9999
178
STF terminal function selection
0–8 / 10–12 / 14 / 16 / 24 / 25 /
37 / 60 / 62 / 64–67 / 9999
60
179
STR terminal function selection
0–8 / 10–12 / 14 / 16 / 24 / 25/
37 / 61 / 62 / 64–67 / 9999
61
180
RL terminal function selection
0–8 / 10–14 / 16 / 24 / 25 / 37 /
62 / 64–67 / 9999
0
181
RM terminal function selection
1
182
RH terminal function selection
2
183
RT terminal function selection
3
PARAMETER