Mitsubishi Electronics FR-F740EC/E1 Automobile Accessories User Manual


 
22
MITSUBISHI ELECTRIC
FR-F 740 EC/E1
Parameter Overview
0
Torque boost
0–30% 6/4/3/2/1.5/1%
1
Maximum frequency
0–120 Hz 120 / 60 Hz
2
Minimum frequency
0–120 Hz 0 Hz
3
Base frequency
0–400 Hz 50 Hz
4
1. Multi-speed setting (high speed)
0–400 Hz 50 Hz
5
2. Multi-speed setting (middle speed)
0–400 Hz 30 Hz
6
3. Multi-speed setting (low speed)
0–400 Hz 10 Hz
7
Acceleration time
0–360 s / 0–3600 s 5 s / 15 s
8
Deceleration time
0–360 s / 0–3600 s 10s / 30 s
9
Electronic thermal O/L relay
0–500 A / 0–3600 A
Rated current
10
DC injection brake operation frequency
0–120 Hz / 9999 3 Hz
11
DC injection brake operation time
0–10 s / 8888 0.5 s
12
DC injection brake operation voltage
0–30% 4 / 2 / 1%
13
Starting frequency
0–60 Hz 0.5 Hz
14
Load pattern selection
0/1 1
15
JOG frequency
0–400 Hz 5 Hz
16
JOG acceleration/deceleration time
0–360 s / 0–3600 s 0.5 s
17
MRS input selection
0, 2 0
18
High speed maximum frequency
120–400 Hz 120 /60 Hz
19
Base frequency voltage
0–1000 V / 8888 / 9999 8888
20
Acceleration/deceleration reference frequency
1–400 Hz 50 Hz
21
Acceleration/deceleration time increments
0/1 0
22
Stall prevention operation level
0–150% / 9999 /
0–120% / 9999
120% /
110%
23
Stall prevention operation level compensation factor at double
speed
0–150% / 9999/
0–120% / 9999
9999
24
Multi-speed setting (speed 4)
0–400 Hz / 9999 9999
25
Multi-speed setting (speed 5)
0–400 Hz / 9999 9999
26
Multi-speed setting (speed 6)
0–400 Hz / 9999 9999
27
Multi-speed setting (speed 7)
0–400 Hz / 9999 9999
28
Multi-speed input compensation selection
0/1 0
29
Acceleration/deceleration pattern selection
0/1/2/3 0
30
Regenerative function selection
0/2/
0/1/2
0
31
Frequency jump 1A
0–400 Hz / 9999 9999
32
Frequency jump 1B
0–400 Hz / 9999 9999
33
Frequency jump 2A
0–400 Hz / 9999 9999
34
Frequency jump 2B
0–400 Hz / 9999 9999
35
Frequency jump 3A
0–400 Hz / 9999 9999
36
Frequency jump 3B
0–400 Hz / 9999 9999
37
Speed display
0 / 1–9998 0
41
Up-to-frequency sensitivity
0–100% 10%
42
Output frequency detection
0–400 Hz 6 Hz
43
Output frequency detection for reverse rotation
0–400 Hz / 9999 9999
44
2nd Acceleration/deceleration time
0–360 s / 0–3600 s 5s
45
2nd Deceleration time
0–360 s / 0–3600 s / 9999 9999
46
2nd Torque boost
0–30% / 9999 9999
47
2nd V/f characteristics (base frequency)
0–400 Hz / 9999 9999
48
2nd Stall prevention operation current
0–150% /
0–120%
120% /
110%
49
2nd Stall prevention operation frequency
0–400 Hz / 9999 0 Hz
50
2nd Output frequency detection
0–400 Hz 30 Hz
51
2nd Electronic thermal O/L relay
0–500 A / 9999 /
0–3600 A / 9999
9999
PARAMETER