Beck, R&J 11-1_9 Automobile Parts User Manual


 
43
RealTimeClock Submenu
(Block 4M)
This menu allows the date and time to be set.
The settings are as follows:
1. RTC Day - Numerical entry sets the day of the
month.
2. RTC Month - Numerical entry sets the
month.
3. RTC Year - Numerical (4 digit) entry sets the
year.
4. Hour (24) - Numerical entry sets the hour of
the day (1–24).
5. Minute - Numerical entry sets the minute of
the hour.
Calibration Trim Menu
(Block 3G)
This menu displays/sets drive calibration
values:
1. PresCPS V - Displays the present value of
the internal Position Sensor voltage. This
value can also be measured at TP4(+) and
TP1(–) on the DCM-2 board. This value can
be edited to trim the Position Sensor.
2. Loop(Dem) - Displays the Demand signal
as measured at the field wiring terminals.
When the Demand control loop signal is being
overridden by a special mode of operation,
the effective Demand will not correspond to
the mA value. This value can be edited to trim
the Demand to ensure accurate measurement
of the analog signal. Demand can only be
trimmed at 4.0 mA and 20.0 mA.
3. Feedback - Displays the mA signal
representing the output shaft position as
measured at the eld wiring terminals. This
value can be edited.
4. Trq/Thrust - Displays the load measured at
the output shaft as a percentage. This value
can be edited.