Beck, R&J 11-1_9 Automobile Parts User Manual


 
41
Diagnostics Menu
(Block 3F)
This menu provides access to all the DCM-2
stored online diagnostic information about drive
operation. The menu provides six submenus
accessing drive statistics and online drive status.
Status Submenu
(Block 4H)
This menu provides access to six submenus
displaying various drive status settings: LED
Status, Operating Status, Switch Status, Local
Cntrl Status, CW Inhibitors, and CCW Inhibitors.
LED Status Submenu
(Block 5B)
This menu displays the ON or OFF status of
each of the LEDs on the DCM-2. See below.
Operating Status Submenu
(Block 5C)
This menu displays the ON or OFF status of
eight drive parameters: Dem Limits, Pos Limits,
Temp Limits, Torq Limits, Over-Torq Stop, Stalled,
Feedback Open, and Switch Block. See below.
Switch Status Submenu
(Block 5D)
This menu displays the ON or OFF status
of the eight switch parameters: LV Lim CCW,
LV Lim CW, OvrRd CCW, OvrRd CW, OvrRd
Stop, HndSw CCW, HndSw CW, and HndSw
AUTO. The Switch Status menu displays the
status of the CW/CCW control override input, the
STOP control override or if the Handswitch is in
the CW/CCW or AUTO position.
Local Control Status Submenu
(Block 5E)
This menu displays the ON or OFF status of
ve local interface drive parameters: Calibrate,
Set Pos 100%, Set Pos 0%, Set Dem 100%, and
Set Dem 0%. The Local Control Status submenu
indicates which buttons on the Local Control
board are pressed.
LED HART
NAME NAME DESCRIPTION
STAT "Status" "ON indicates that an operating
condition is inappropriate see
Operating Status menu'"
REV "Reverse" "ON indicates that the Demand
signal is less than the Position
signal"
FWD "Forward" "ON indicates that the Demand
signal is greater than the
Position signal"
DEM_ERR "Demand" "ON indicates that a Demand
error condition exists check the
operating mode settings"
POS_ERR "Position" "ON indicates that the Position
signal may be out of range or
saturated"
TORQ_ERR "Trq/Thrust" "ON indicates that the Torque
or Thrust sensor signal may
be out of range or saturated"
STALL_ERR "Stall" "ON indicates that the motor
may be stalled"
TEMP_ERR "Temperature" "ON indicates that a
temperature fault exists"
FB_ERR "FB Open" "ON indicates that the
feedback loop is open or
out of range"
STOP_ERR "Limit" "ON indicates that a limit
switch has been triggered"
ACKN_ERR "Acknowledge" "Acknowledge indicator is
active"
CONDITION DESCRIPTION
DEMAND_LOS "The Demand Signal is outside
of the intended limits (see
Demand Setup menu)"
TRQ_THRUST_OVERRANGE "The Torque/Thrust is greater
than the output rating"
STALL "Stall condition has been
detected (see General Setup
menu)"
OVERTRQ_THRUST_ "Motor power has been removed
PROTECTION due to excessive output thrust"
STOP_OR_LIMIT "Motor power is blocked check
switches"
FEEDBACK_ "The Feedback signal is
DISCONNECTED enabled but the loop is open"
TEMPERATURE_ "The temperature is outside of
OVERRANGE –40F to 185F"
POSITION_OVERRANGE "The Position signal is less
than –5% or greater than 105%"