FC-21 Flow Computer
Sub-menus Display Notes
6.4.10
SETUP
FLOW INPUT
(Analog)
SETUP FLOW INPUTS
EXCITATION VOLTAGE
5v 12v 24v
FLOW INPUT TYPE
Pulse Analog
ANALOG SIGNAL TYPE
Voltage Current
ANALOG VOLTAGE RANGE
0-10V 0-5V 1-5V
ANALOG CURRENT RANGE
4-20mA 0-20mA
LINEARIZATION TYPE
Linear Sqrt LinTbl
LINEAR TABLE KA
APR01:######## gal/m
LINEAR TABLE KA
CFr01:########
FLOW LOW SCALE
####### gal/m
FLOW FULL SCALE
####### gal/m
LOW FLOW CUTOFF
####### gal/m
LOW FLOW RATE ALARM
####### gal/m
HIGH FLOW RATE ALARM
####### gal/m
Advance To
SETUP AUX INPUT
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Press ENTER to begin setup of the Flow
Input.
Select the desired Excitation Voltage.
Press ENTER when Analog is flashing to
configure the flow input for Analog signals .
Choose Analog Signal Type.
If Voltage selected,
Choose desired Voltage Range.
If Current selected,
Choose desired Current Range.
Select the desired Linearization Type.
If LinTbl selected,
Enter the desired Apparent Input Flow (APR) /
Correction Factor (CFr) pair for each point in
the Linearization Table.
NOTE: Enter 0 for APR value of any point
(other than APR01) to exit the routine
and use the values entered up to that
point.
Enter the low flowrate corresponding to the
low analog signal.
Enter the High flowrate corresponding to the
High analog signal.
Enter the desired Low Flow Cutoff.
Enter the desired volumetric Low Rate Alarm.
This will trigger an alarm message if alarm
conditions occur. The relays are not affected.
Enter the desired volumetric High Rate Alarm.
This will trigger an alarm message if alarm
conditions occur. The relays are not affected.
Through
16 Points