FC-21 Flow Computer
3.4 Batching
Measurements:
A flowmeter measures the actual volume in a liquid line. A temperature
sensor can also be installed to correct for liquid thermal expansion (see
3.2 Corrected Volume).
Calculations:
For Flowmeters with Pulse Outputs, Volume flow is calculated using
the flowmeter frequency output and the user entered K-Factor.
For Flowmeters with Analog Transmitters, Volume flow is calculated
using the measured flowmeter signal and the user entered scale settings.
Corrected Volume is calculated using the flow and temperature inputs
as well as the thermal expansion coefficient stored in the flow computer.
Output Results:
Display Results
Flow Rate, Batch Total, Non-Resettable Total, Temperature, Density
Analog Output
Rate, Total, Temperature or Density
Pulse Output
Total
Relay Outputs
Batch Total, Rate, or Temperature Alarms
Applications:
Batching and monitoring flow and total of any liquid. Batching is
accomplished via relays and datalogging is available via analog (4-
20mA) and serial outputs.
Batching
Batching Illustration
Calculations
Volume Flow
As calculated in section 3.1
Corrected Volume Flow
(Temp. Transmitter)
Corrected Vol. Flow = volume flow * (1 - Therm.Exp.Coef. *(Tf-Tref))