Toshiba 18 - 1250 A Remote Starter User Manual


 
TE Series Digital Solid State Soft Starters 18 – 1250A
80
Fn#
Function
Type
Setting Function Description / Range
Timer
Initiated
By…
Motor
Starts
When…
Motor
Stops
When…
Timer
Reset
When…
F030
Process
Control
Timer
Mode
0 No Process Control Timer operation (default setting from factory)
1
Minimum (Batch) Run Timer
(works the same with or without TCC
control)
Start
command
and/or
TCC
Start
command
Time
Expires,
Trip, or
Stop
Command
Time
Expires +
Stop
command
only
2
Permissive Run Timer, without TCC
(F032 =0, “One Shot”)
Start
command
Start
command
Time
Expires
Permissive Run Timer, with TCC
(F032 = 2 thru 8)
TCC Start
Event
only
Next SEC
only
F031
Process
Timer
Value
Run
Time
Value
Timer value setting used by F030
Range: 1 – 9999 minutes (166.65
hours)
--- ---
Per F030
setting
F032
24 hr /
7 day
Time Clock
Controller
0 One-Shot, follows Start command only
Start
command
Start
command
Per F030
setting
Per F030
setting
1 Loop the Start Even Cycle (SEC) daily
24hr Real
Time
Clock on
day of
program
change
Per F030
setting
Per F030
setting
Continuous
unless
program is
changed
2 Loop the 24hr SEC every other day
3 Loop the 24hr SEC every 3
rd
day
4 Loop the 24hr SEC every 4
th
day
5 Loop the 24hr SEC every 5
th
day
6 Loop the 24hr SEC every 6
th
day
7 Loop the 24hr SEC one day per week
8
Single 24hr SEC, without repeating
(until programmed again)
Change of
Program
F033 Event #1
Start
time
24hr TCC Start Time for Event #1
F032 =1-8
Continuous
unless
program is
changed
F034 Event #2
Start
time
24hr TCC Start Time for Event #2
F035 Event #3
Start
time
24hr TCC Start Time for Event #3
F036 Event #4
Start
time
24hr TCC Start Time for Event #4
F037 Event #5
Start
time
24hr TCC Start Time for Event #5
F038 Event #6
Start
time
24hr TCC Start Time for Event #6
F039 Event #7
Start
time
24hr TCC Start Time for Event #7
Chart APP 4.1 Process Timer and TCC Operations Logic Chart
NOTE:
These functions may interact with the Coast Down Lockout (F048),
Stars-per-Hour Lockout (F049), Minimum Time Between Starts
(F050), Auto-Reset (F052) and Restart Delay Time (F028) functions
if enabled. Be sure to read and understand descriptions of those
functions, then check settings before using the Process Control
Timer.