5.5.7 Process Timer Features
5.5.8 Current and Ground Fault Protection Features
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F030
Run Timer and Time Clock Controller Modes
Run Timer Selection
0 = Disabled (No timer operation)
1 = Minimum (Batch) Run Timer
2 = Permissive Run Timer
1
0
Disabled
5.6.7
and
Append.
4
F031
Run Timer Time
for use in F030 above
1-9999 minutes after a Start
Command or Start Event from TCC
1 1
F032
24hr
Time Clock Controller (TCC)
Start Event Mode.
Chose “One Shot”
or 1 to 7 “Start Events”
from F033 – F039
Run time for this mode comes
from F030 above.
Start Event Cycle (SEC) Settings.
1 = Loop SEC every day
2 = Loop SEC every 2
nd
day
3 = Loop SEC every 3
rd
day
4 = Loop SEC every 4
th
day
5 = Loop SEC every 5
th
day
6 = Loop SEC every 6
th
day
7 = Loop SEC one day per week
8 = Single 24hr SEC
(until programmed again)
0 = One Shot: Start Event comes
from Start command only
1
0
One Shot
F033 Start Event #1 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
F034 Start Event #2 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
F035 Start Event #3 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
F036 Start Event #4 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
F037 Start Event #5 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
F038 Start Event #6 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
F039 Start Event #7 Start Time 00:00-23:59 (hh:mm) or OFF 1 OFF
Table 5.5.7: Run Timer and Time Clock Controller Function Group
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F040
Current and Ground Fault Protection
Current Imbalance Trip
0 = Disabled, or
5 - 30% imbalance
1%
0
Disabled
5.6.8
F041 Current Imbalance Trip Delay 1 - 20 seconds 1 second
2
seconds
F042 Over Current Trip
0 = Disabled, or
100 - 300% of motor FLA
1%
0
Disabled
F043 Over Current Trip Delay 1 - 20 seconds 1 second 1 second
F044 Under Current Trip
0 = Disabled, or
10 - 90% of motor FLA
1%
0
Disabled
F045 Under Current Trip Delay 1 - 60 seconds 1 second
2
seconds
F046 Ground Fault Trip
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1%
0
Disabled
F047 Ground Fault Trip Delay 1 - 60 seconds 1 second
2
seconds
Table 5.5.8: Current and Ground Protection Features Group