Toshiba 18 - 1250 A Remote Starter User Manual


 
TE Series Digital Solid State Soft Starters 18 – 1250A
33
5.5.9 Lockouts, Reset and Internal Protection Functions
5.5.10 Output Relay Programming Features
NOTE:
Check wiring to each relay before changing programming to ensure
there are no unintended consequences.
Relays programmed to some protection features will not operate if
function is disabled elsewhere.
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F048
Lockouts, Reset and Internal Protection
Coast Down (Back Spin)
Lockout Timer
0 = Disabled, or 1 - 60 minutes 1 minute
0
Disabled
5.6.9
F049 Maximum Starts per Hour 0 = Disabled, or 1 – 10 starts 1
0
Disabled
F050
Minimum Time Between
Starts
0 = Disabled, or 1 - 60 minutes 1 minute
0
Disabled
F051 Internal Protection Settings
1 – 127
See“ F051 Definition Table”
1
127
Enable all
5.6.9.a
F052
Auto Reset
on Selected Faults
Fault Preferences 1 – 12
See Table 5.6.8:
”Auto-Reset Selected Faults”
1
4,
Phase
Loss only
5.6.9.b
F053 Auto Reset Attempts 0 = Disabled, or 1-10 attempts 1 1
F054
Restart Delay Time Value
Readout (for F028)
0-999 Minutes 1 0
5.6.9.c
F055
Coast Down Timer Value
for F048
1-3600 Seconds 1 0
F056
Starts Per Hour Timer Value
for F049
1-3600 Seconds 1 0
F057
Starts Per Hour
For F049
1-10 Starts 1 0
F058
Time Value Between Starts
for F050
1-3600 Seconds 1 0
F059
Thermal Capacity to Start
for F005
0-100 % Thermal Capacity 1 0
Table 5.5.9: Lockouts, Reset and Internal Protection Group
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Section
F060
Output Relays
Aux Relay 1 setting
Operation # 1 – 26: see
”Aux. Relay Settings Chart”
1 1
5.6.10
F061 Aux Relay 2 setting
Operation # 1 – 26: see
”Aux. Relay Settings Chart”
1 2
F062 Aux Relay 3 setting
Operation # 1 – 26: see
”Aux. Relay Settings Chart”
1 16
F063
Aux. Relay Delay Timer
(for Operations 23-26)
0 (Disabled), or 1-999 seconds 1 second
0
No Delay
F064 Reserved for factory use
Table 5.5.10: Output Relay Function Group