Toshiba 18 - 1250 A Remote Starter User Manual


 
TE Series Digital Solid State Soft Starters 18 – 1250A
75
Display
Press
Key...
Shows...
Means...
Starting at
Function #30
Default Setting
of Function #30
Set F030 = 1
Minimum Run Timer
F030
0000
0001
Return to
Function # Display
Figure App 4.1:
Programming the Minimum Run Timer Functions
Example: Process Timer for Well Pump
F031
READ
ENTER
x 3
Change Setting
to 30 minutes
0030
READ
ENTER
En d
Value Accepted
(flashes once)
Change to
F031
F031
Default Setting
of Function #31
0000
READ
ENTER
READ
ENTER
En d
Value Accepted
(flashes once)
Cycle Control Power to Accept Changes
Example: Figure App 4.1
Minimum Run (Batch) Timer
An irrigation pump needs to come on when called for by a soil
moisture control system, and run for ½ hour. If during that ½
hour the well level drops and shuts the pump down, the pump
needs to restart when the well recovers and finish the ½ hour
pump time.
Set F030 to [0001] for Minimum Run Timer.
This will ensure that when the well level recovers and resets
the run command, the starter will finish the time sequence.
Set F031 to [0030] (minutes)
This is the Run Time that ensures the proper amount of
irrigation getting to the crop.
(Not Shown)
Ensure F032 is set to [0000] for One Shot
This will allow the Start command provided by the external
control system to engage the starter at any time it is required.
(Another example of this function used with the Time Clock
Controller is provided further on)
NOTE on interaction with other functions:
When used with F028 (Auto-Restart Delay), the Minimum Batch
Timer will not resume counting down until F028 has expired and the
starter has restarted. When used with 3 wire control, it may be
necessary to maintain a Start Command until after F028 has
expired, or repeat it if momentary.
When used with F049 – F050 (Lockout Protection features), the
Minimum Batch Timer will not resume counting down until those
settings have been satisfied and the TE Series starter has
restarted. When used with 3-wire control, it may be necessary to
maintain a Start Command until after they are satisfied, or repeat it
if momentary.
When used with the Pump Flex Decel feature, the Decel Time
(F027) is counted as part of the Batch Run time for this feature.