Toshiba 18 - 1250 A Remote Starter User Manual


 
TE Series Digital Solid State Soft Starters 18 – 1250A
9
2.6.1 Power Terminals:
Connection points for units of 160A and below are saddle clamps
suitable for stranded wire. Connection points for units of 210A and
above are bus tabs with pre-drilled holes (see below). Use appropriate
compression or mechanical lugs for termination to these bus tabs.
Suggested wire sizes and tightening torques for factory-supplied
connectors when using conductors rated for 75°C are shown in the
chart below. Always consult local codes and industry standard practices
for proper wires sizes to accommodate voltage drop and ambient
conditions.
Model
Number
Current
Range
Min.- Max.
Suggested
Wire Size
AWG
Tightening
Torque
in.-lbs.
Screw / Bolt
Size
Tightening
Torque
Nm
Suggested
Wire Size
ISOmm
2
TE-18-BP 9 - 18 12
35
1 x M5
(included)
4
6
TE-28-BP 14 - 28 10
10
TE-39-BP 19 - 39 8
16
TE-48-BP 24 - 48 6
16
TE-62-BP 36 - 62 4
45
1 x M8
(included)
5
25
TE-78-BP 39 - 78 3 35
TE-92-BP 46 - 92 2 35
TE-112-BP 56 - 112 2 50
TE-150-BP 75 - 150 0
80
1 x M8
(included)
9
70
TE-160-BP 80 - 160 2/0 70
TE-210-BP or -P 105 - 210 4/0
200
1 x 0.38" hole
(M10)
for User
supplied
lugs
15
120
TE-276-BP or -P 138 - 276 300 kCMIL 150
TE-360-BP or -P 180 - 360 500 kCMIL 300
TE-450-BP or -P 225 - 450 2 x 250 kCMIL 2 x 150
TE-550-BP or -P 275 - 550 2 x 250 kCMIL 2 x 150
TE-718-BP or -P 356 – 718
CF CF
CF CF CF
TE-900-BP or -P 450 – 900
CF CF
CF CF CF
TE-1000-BP or -P 50 - 1000
CF CF
CF CF CF
Table 2.6: TE Series Wire Ranges and Torque Specifications
CF = Consult Factory
2.7 Remote Keypad Mounting
The keypad / operator interface unit can be remotely mounted up to 10’
(3 meters) away from the starter, i.e. on the enclosure door. A remote
mounting kit is necessary, consisting of an adaptor plate, a doorframe
for NEMA 1 or NEMA 12 enclosures and a pre-assembled ribbon cable
available in 1-meter length increments. Detailed assembly instructions
and an enclosure cutout template are included with that kit. See Product
Selection Guide for part numbers of the different kits depending on
NEMA rating and cable lengths.
Figure 2.7
Remote Keypad Mounting Kit
Components
Adaptor Plate
~ ~
~
Ribbon Cable,
1, 2 or 3 meters
NEMA 1 o
r
NEMA 12
Door Frame
TE Starte
r