TE Series Digital Solid State Soft Starters 18 – 1250A
57
5.6.11 Communications
The TE Series starter is shipped from the factory ready to accept
RS-485 Serial Communications using Modbus RTU protocol. Additional
detailed instructions on accomplishing communications are available in
a Serial Communication Supplement to this manual. F065 – F067 are
used to set the communications parameters in the starter for use by the
adaptor module. F068 determines how the Start / Stop functions work
through the comm. port.
F065 = Communications
Factory Setting = 0 (Disabled)
Range = 0 – 2
This enables serial communications with remote monitoring and
control systems and sets the format for Modbus RTU protocol.
Once Enabled, the local start / stop inputs are altered to avoid
inadvertent starting. See F068 for details.
When F065 = 0, communications are disabled.
When F065 = 1, uses the std 11 bit Modbus format w/ parity bit.
When F065 = 2, a non-standard 10-bit format without a parity
bit is used to accommodate some systems using this method.
F066 = Baud Rate
Factory Setting = 9.6 KB
Range = 4.8 to 19.2 KB
Set value to either 4.8 KB, 9.6 KB or 19.2 KB and match the
setting of the host device.
F067 = Modbus Address
Factory Setting = 1
Range = 1 – 247
The Modbus communications protocol allows each node to
have up to 247 connected devices but each must have a unique
address. Two devices with the same address will result in a
communications error.
F068 = Remote Starter Control
Factory Setting = 0 (disabled)
Range = 0 – 3
Use this to program how the TE Series starter is to be
controlled when using serial communications.
When F068 = 0, the starter can be monitored by the Comm
port, but not controlled.
When F068 = 1, the starter will be controlled by the comm port.
In addition, the Start / Stop inputs are altered as follows: The
hard-wired Start command is put in “AND” logic with the Comm
port; both Start commands must be on for the TE to start. The
Stop function is put in “OR” logic; either the Comm. port Stop
command OR the hard-wired Stop will cause the TE to stop.
When F068 = 2, the TE starter is in full control of the Comm.
port only. Local Start / Stop inputs become completely inactive.
Use this function only when controlled shutdown is a priority.
When F068 = 3, the TE starter will change the function of the
Jog / Remote Input to cause a switch between the functions of
setting 0 and setting 1 as listed above. When the input is open,
the starter will respond to the Comm port as per setting 0
above. When the Jog / Remote Input is closed, the starter will
respond as per setting 1 above. Use this function if it is
necessary to have a return to local start/stop control should the
communications system fail or become disconnected.
N C
JOG
RAM P2
PTC
OPTO
Figure 5.6.11:
Local - Remote Control Connections to TB-1
Only when F068 = 3
Local Remote
6 7 8
Special Note when using Serial Comm:
When F068 = 3, the function of the Jog /
Remote Input on TB-1 terminals 7 and 8 will
change. Closing the Input will cause the
Comm. port control to function as per setting
1. Leaving the input open will cause the
Comm. port to function as per setting 0.
When F068 = 1, 2 or 3, the Jog function will
cease to operate. Since Jogging is a local
function, set F068 to 0 when using it.