5.6.13 Fault History and Statistical Data
F085 – F097 contain the Fault History and Statistical data about the
Run Mode.
5.6.13.a Fault History
Fault codes for each of the three latest events are stored with time
and date stamps; see Chapter 7 for a complete list of fault codes
and corresponding error displays.
Time stamps use the 24hr HH.MM format, so for example 3:19 PM
would display as [15.19]
Date stamps use the MM.DD format, so for example September 3
rd
would display [09.03]
Fault #1
(Latest Fault)
Fault #2
(Previous Fault)
Fault #3
(Oldest Fault)
Fault code:
(See Chapter 7)
F085 F088 F091
Time Stamp
(HH.mm)
F086 F089 F092
Date Stamp
(MM.DD)
F087 F090 F093
Table 5.6.13.a: Fault History Configuration
F085 = Latest Fault Code (Fault #1)
Factory Setting = 0 (No Fault)
Range = 0 – 27
This Function displays the Fault Code of the latest fault event.
F086 = Time Stamp of the Latest Fault
Factory Setting = 00.00 (No Fault)
Range = 00.00 – 23.59 (24hr time format)
This Function displays the time of the latest fault event.
F087 = Date Stamp of the Latest Fault
Factory Setting = 00.00 (No Fault)
Range = 01.01 – 12.31
This Function displays the date of the latest fault event.
F088 = Same as F085 except for the Previous Fault (Fault #2)
F089 = Same as F086 except for the Previous Fault.
F090 = Same as F087 except for the Previous Fault.
F091 = Same as F085 except for the Oldest Fault (Fault #3)
F092 = Same as F086 except for the Oldest Fault
F093 = Same as F087 except for the Oldest Fault