8.2.14 Still Water Zero Adjustment
Zero adjustment is performed with the fluid held still in the detector's measurement pipe.
Switch operation
Display example
Description
Select "ZERO ADJ" from the
configuration item selection menu.
The current flow rate measurement value
appears.
Then push and hold longer.
* Pushing returns you to the setting
menu.
The title display changes to ADJ READY,
and the converter is ready for zero
adjustment.
* Pushing returns you to the previous
screen.
Pushing starts zero adjustment.
Zero adjustment ends in several seconds and
the flow rate measured value appears.
Pushing returns you to the setting
menu.
Note 1: To start still water zero adjustment, push and hold longer.
Note 2: Still water zero adjustment is possible only when the flow rate value is within the range of
±1.25 m/s.
Note 3: If you want to cancel the adjustment when ADJ READY is displayed, push . This
returns you to the state showing the flow rate measurement value on the screen.